Efek Kegagalan Alat Flue Gas Desulphur Terhadap Tegangan Lewat Denyar Isolator

Tedy Juliandhy, T. Haryono, Suharyanto Suharyanto

Abstract


Abstract— Flashover is a disorder condition that occurs in the form of sparks appearing between insulators or electrical component of high voltage. This can occur due to insulation failure of the high voltage system. Failure of insulation in high voltage insulators in Tanjung Jati B substation Jepara is one of the causes of acid rain due to the condensation of smoke from the Tanjung Jati B power plant chimney. Acid rain arises due to failure Flue Gas Desulphur ( FGD ) devices were installed in the plant to reduce gas emissions as a condition of eco-friendly power plant that is planned by the government through the department of Environment . The real action is taken to dismiss the notion that power plant fuel coal is one of the industries that emit SOx and NOx emissions are high on operational processes . The effects of gas emissions is one of the causes of acid rain on the environment . The amount of acidity of acid rain that occurred in the industrial area will always affect the high voltage power lines that distribute power in operation . Sometimes the equipment functions as an insulator in high voltage substations that distribute power at 500 kV network SUTET JAMALI network on the island of Java in a system of operation is interrupted because of pollutants attached to the insulator . Rain with a pH between 4-5 categorized as acid rain and the test affects the time of the flashover voltage drop of 145.5 kV – 142.5 kV of the working voltage , this causes an insulator as insulation materials can be minimized distance insulator surface so that termites can affect the resistance of an insulator in its function as a tool to restrain the occurrence of flashover voltage from voltage parts.

Intisari— Tegangan Lewat denyar (flashover) adalah fenomena pelepasan muatan bersifat merusak yang melintasi seluruh bagian permukaan isolator. Pelepasan muatan ini disebabkan pembebanan medan listrik pada permukaan isolator yang melebihi harga ketahanan elektriknya. Penyebab terjadinya tegangan lewat denyar adalah pengotoran permukaan isolator, hujan asam, surja hubung dan surja petir. Tegangan lewat denyar atau flashover ini berupa fenomena y loncatan api yang terjadi antara isolator atau komponen listrik tegangan tinggi. Hal ini dapat terjadi akibat gagalnya isolasi sistem tegangan tinggi tersebut.
Salah satu penyebab Kegagalan isolasi pada isolator tegangan tinggi di Gardu induk Tanjung Jati B Jepara adalah timbulnya hujan asam akibat kondensasi asap yang keluar dari cerobong PLTU Tanjung Jati B. Hujan asam timbul karena kegagalan peralatan Flue Gas Desulphur ( FGD ) yang dipasang di PLTU untuk mengurangi gas emisi sebagai persyaratan pembangkit listrik ramah lingkungan yang diprogramkan pemerintah melalui departemen Lingkungan Hidup. Tindakan nyata ini dilakukan untuk menepis anggapan bahwa PLTU dengan bahan bakar batubara merupakan salah satu industri yang mengeluarkan gas emisi SOx dan NOx yang tinggi pada proses operasionalnya. Efek gas emisi ini merupakan salah satu penyebab terjadinya hujan asam pada lingkungan. Banyaknya kadar keasaman hujan asam yang terjadi di daerah industri akan selalu berpengaruh terhadap jaringan listrik tegangan tinggi yang sedang beroperasi menyalurkan daya listrik. Adakalanya fungsi peralatan tegangan tinggi seperti isolator di gardu induk yang menyalurkan daya listrik pada jaringan SUTET 500 kV pada jaringan JAMALI di pulau Jawa terganggu dalam sistim operasinya karena polutan yang menempel di isolator. Hujan dengan pH antara 4 – 5 dikategorikan sebagai hujan asam dan pada pengujian ini mempengaruhi penurunan tegangan saat terjadinya flashover sebesar 145.5 kV – 142.5 kV dari tegangan kerja, hal ini menyebabkan isolator sebagai bahan isolasi dapat diperkecil jarak rayap permukaan isolatornya sehingga dapat berpengaruh terhadap ketahanan suatu isolator dalam menjalankan fungsinya sebagai alat untuk menahan terjadinya kegagalan tegangan lewat denyar (Flashover) dari bagian-bagian yang bertegangan.

Kata kunci— Kondensasi, FGD, PLTU, Hujan asam, SUTET, JAMALI, pH, Flashover


Full Text:

PDF

References


Vosloo, WL. A Comparison of the Performance of High Voltage Insulator Materials in a Severity Polluted Coastal Environment. PhD Dissertataion, Departement of Electrical and Electronic Engineering, University of Stellenbosch, South Africa. 2002.

Chuyan Zhang, Liming Wang, Zhicheng Guan, Fuzeng Zhang. Pollution Flashover Performance of Full-scale 800 kV Converter Station Post insulators at High Altitude Area. IEEE: 1070-9878/13. 2013.

Richard D.Tabors. Coal to Natural Gas Seasonal Fuel Switching; An Option for Acid Rain Control. IEEE : 0885-8950/89/0500-0457. 1989

Paul McGarth. Accelerated Aging of Insulators Under Acid Rain Condition. IEEE : 0-7803-5931-3/00. 2000.

Mohammed Amin, Raji Sundararajan. Performace of Silicone Rubber Insulators under Acid Rain and Multistress Condition. IEEE: 978-1-4244-8286-3/10. 2010.

BX. Du, T. Han, X. Cheng, Jie Lie. Characterization of Surface Discharge as Indicator for Hydrophobicity Evaluation of Silicone Rubber Insulators. IEEE : 1070-9878/12. 2012.

Diklat PLN. Basic Trainee Transmission and Protection for 500 kV/ 150 kV. Ungaran – Semarang 2006.

Bonggas L. Tobing. Peralatan Tegangan Tinggi, Edisi kedua. Penerbit Erlangga 2002.

Nurlailati. Analisis Degradasi Permukaan Bahan Isolasi Resin Epoksi Karena Proses Penjejakan Dan Erosi. Tesis Fakultas Teknik Jurusan Teknik Elektro Universitas Gadjah Mada, Yogyakarta.2011.

Ika Novia Anggraini. Pengaruh Komposisi Bahan Isolasi Resin Epoksi Dengan Bahan Pengisis Silicone Rubber Terhadap Proses Tracking Dan Erosi. Tesis Fakultas Teknik Jurusan Teknik Elektro Universitas Gadjah Mada, Yogyakarta.2010.

Gorur, R. S. Et.al. A Laboratory Test for Tracking and Erosion Resistance of HV Outdoor Insulation”, IEEE Transaction on Dielectrics and Electrical Insulation, Vol 4 No 6. 1997.

Kugami, S dan Yoshimura, N. Tracking and Erosion of HTV Silicone Rubber and suppression Mechanism of ATH ”, IEEE Transactions on Dielectric and Electrical insulation, Vol 8 No.2. 2001

Hartono. Acid Rain. Paper Pasca Sarjana Universitas Indonesia 2005.

Raji Sundararajan. Long Term Acid Rain Multistress Performance of Thermoplastic and Thermoset Polymeric Insulators. IEEE : 978-1-4244-6653-5/10. 2010.

Valdi Rizki Yandri, Nurhatisyah. Fenomena Flashover Akibat Arus Bocor Pada Isolator Keramik dan Resin Epoxy. Jurnal Teknik Elektro ITP Vol.2 no. 2, Juli 2012.

Lanto M. Kamil Amali. Analisis Pengujian Arus Bocor Line Post Insulator 70 kV Yang Terkontaminasi Polutan Industri. Jurnal ilmiah FORISTEK Vol. 2 no.1, Maret 2012.

Diklat Pembangkitan Tanjung Jati B. Basic Trainee for power Plant. Oktober 2006.

Paul Breeze. Power Generation Technologies. Page 29-30. First published 2005.




DOI: http://dx.doi.org/10.22146/jnteti.v3i2.68

Refbacks

  • There are currently no refbacks.


Copyright (c) 2016 Jurnal Nasional Teknik Elektro dan Teknologi Informasi (JNTETI)

JNTETI (Jurnal Nasional Teknik Elektro dan Teknologi Informasi)

Departemen Teknik Elektro dan Teknologi Informasi, Fakultas Teknik Universitas Gadjah Mada
Jl. Grafika No 2. Kampus UGM Yogyakarta 55281
+62 274 552305
jnteti@ugm.ac.id